Electro-Chemical Devices has announced the plug-and-play TC-80 Total Chlorine Analyser, which offers simplified water monitoring and treatment processes, easy installation and less maintenance for lower ownership costs.
The analyser monitors total chlorine in drinking water, rinse water, cooling water or other fresh water samples from 0.05-20ppm chlorine as the standard range or 0.005-2.000ppm with the low range sensor. Its plug-n-play design installs quickly right out of the box. It has an advanced panel mount design includes built-in flow control, which eliminates the need for complicated pressure regulators and rotameters. Built-in automatic pH compensation also eliminates the need for expensive reagents to reduce maintenance and life-cycle costs.
The analyser features a panel mount design that incorporates a constant head flow control device, a pH sensor, a chlorine sensor and ECD’s T80 analyser/transmitter conveniently mounted on a PVC panel. Connect the sample and drain lines, next connect the power and outputs, and the TC-80 is ready to use. It is calibrated at the factory before shipment, which is accomplished by DPD comparison.
It is available with either 110-240VAC or 24VDC power. It graphically displays both the Total Chlorine and pH allowing for easy trend analysis. The standard configuration has two 4-20mA outputs and three alarm relays.
As for cleaning, the analyser is available with an Auto Clean option that includes a solenoid actuated spray cleaner using either 30psi process water or air. An easily adjusted timer controls the period and duration of the cleaning cycle.